变频器恢复出厂参数是什么
1、变频器恢复出厂参数是什么?
1. What is the recovery of the factory parameters by the frequency converter?
FP-01=1
FP-01=1
2、请问变频器F1电机参数中【电机漏感抗】是指定子漏感抗还是转子漏感抗?
2, please F1 inverter motor parameters in motor [] refers to the leakage inductance of stator leakage inductance and rotor leakage inductance?
定子漏感抗=转子漏感抗=电机漏感抗
The stator leakage inductance = rotor leakage inductance = motor leakage inductance
3、变频器能否查看之前的故障信息?
3. Can the frequency converter check the previous fault information?
可以,比如MD380可以通过参数F9-14~F9-17查看最近的三次故障代码信息。
Yes, for example, MD380 can see the latest three fault code information through the parameter F9-14~F9-17.
4、MD200的A组参数说明书中有,但是变频器里看不到?
4, MD200 A group parameter instructions, but can not be seen in the frequency converter?
A0组为默认隐藏组参数,设置FP-02=111即可(十位为A组参数显示,个位为U组参数显示;FP-02默认为1)。
The A0 group is the default hidden group parameter, and the FP-02=111 is set (ten bits are displayed for A group parameters, the bits are displayed for U group parameters; the default is 1).
5、MD300的说明书中F0-13(DO输出选择)只有0-3,为什么变频器中有4这个选项?
5, the F0-13 (DO output selection) in MD300's specification is only 0-3. Why is there 4 in the frequency converter?
MD300的14#FDT功能非标中有功能4:FDT功能选择。
MD300's 14#FDT function non - standard has functional 4:FDT function selection.
6、MD330中FH-65(锥度模式)的两种锥度模式如何计算?
6, how do the two taper modes of FH-65 (taper mode) be calculated in MD330?
1.FH-65=0曲线锥度是按照F=F0(1-K*(D0+D1)/(D+D1))的曲线
The taper of the 1.FH-65=0 curve is according to the curve of F=F0 (1-K* (D0+D1) / (D+D1))
2.FH-65-1直线锥度则是按照FH-61~FH-64的锥度拐点及张力锥度来决定的;
The 2.FH-65-1 linear taper is determined by the taper of FH-61~FH-64 and the taper of tension.
3.注意:MD330中FH-09(张力锥度)只适用于收卷模式。
3. note: the FH-09 (taper of tension) in MD330 is only applicable to the winding mode.